Diode Current Source Property Tree

Each diode source device will be represented by the following property tree structure:
  • ADAPTER:Endpoint=[NAME=DIODESOURCE, PORT=10009]
  • STATE:BasdaServiceStateMachine=ONLINE
  • LOGGER.REMOTE = true
  • LOGGER.LEVEL=WARNING
  • SVC
    • LOAD = [NAME=DiodeSource, LIB=ArgosBasdaServiceDiodeSource]
    • DEVICES = [DIODESOURCE1]
    • CFG.INTERVAL = 2000 +UNIT=millisecond
    • RECONNECTION_INTERVAL = 4000 +UNIT=millisecond
  • DEV![0..9] = "Drag and drop this node to get a GUI"+UI:String="$INSROOT/share/ui/ArgosDiodeSource.ui"
    • NAME="Diode Current Source"
    • LOAD=[NAME=DIODESOURCE1, LIB=ArgosBasdaDeviceDiodeSource]
    • CON=tcp://192.168.3.171:5024
    • NAME=DIODESOURCE
    • DIODE1.CURRENT:Float=0.040 +UNIT="Amper" +MIN=0.021 +MAX=0.701 +STEP=0.02 +ADJUST=true ActorMinMax
    • DIODE2.CURRENT:Float=0.040 +UNIT="Amper" +MIN=0.021 +MAX=0.701 +STEP=0.02 +ADJUST=true ActorMinMax
    • DIODE3.CURRENT:Float=0.040 +UNIT="Amper" +MIN=0.021 +MAX=0.701 +STEP=0.02 +ADJUST=true ActorMinMax
    • DIODE1.MEASURED_CURRENT:Float
    • DIODE2.MEASURED_CURRENT:Float
    • DIODE3.MEASURED_CURRENT:Float
    • DIODE1.STATE=false
    • DIODE2.STATE=false
    • DIODE3.STATE=false
    • DIODE1.DEVICE_STATE:bool
    • DIODE1.DEVICE_STATE:bool
    • DIODE1.DEVICE_STATE:bool
    • TEMPERATURE_UNIT="Celsius"
    • CURRENT_UNIT="Amper"
The lines in bold fonts are updated dynamically by the Diode Current Source service. Their attributes, like alarm thresholds, or Min-MAx values can be overwritten in the configuration file.

Simulator

This device is used in the basda service to simulate the behavior of the Diode Current Source devices. It can be used to simulate communication and / or initialization situations. The simulator has the same properties described above, and adds the following ones:

  • DEV![0-9]
    • INITIAL_CONNECTION_FAILS:bool
    • COMMUNICATION_FAILS_AFTER_CONNECTION:int
    • RECONNECTION_FAILS_AFTER_COMMUNICATION_FAILS:int
where

  • INITIAL_CONNECTION_FAILS set to true causes a connection exception. The service tries to reconnect after (RECONNECTION_INTERVAL) seconds.
  • COMMUNICATION_FAILS_AFTER_CONNECTION causes a communication error while working after N loops.
  • RECONNECTION_FAILS_AFTER_COMMUNICATION_FAILS simulates a reconnection error during N times.