In the event that mirror ventilation does not automatically start, follow this procedure to manually start and stop a defrost cycle:
To Start Manual Defrost
In ECS > MV tab
Click/open the
Display Valve Control Panel
On the offending side, switch the control and modulating valves to
Manual
mode
Switch
Normally Closed
valves to
Open
Switch
Normally Open
valves to
Closed
Set the modulating valves to
25%
open
Click/open the
Display Heater Control Panel
On the offending side, switch the defrost heaters to
Manual
mode
Click
Run
on both heaters
To Stop Manual Defrost
Following the above, undo the steps:
Set Defrost Heaters to
Automatic
mode
Set Normally Open Valves to
Automatic
mode
Set Normally Closed Valves to
Automatic
mode
Set Modulating Valves to
Automatic
mode
--
SteveAllanson
- 08 May 2013
E
dit
|
A
ttach
|
P
rint version
|
H
istory
: r1
|
B
acklinks
|
V
iew wiki text
|
Edit
w
iki text
|
M
ore topic actions
Topic revision: r1 - 08 May 2013,
SteveAllanson
Operators
Log In
Toolbox
Create New Topic
Index
Search
Changes
Notifications
RSS Feed
Preferences
Users
Groups
Webs
ARGOS
AdaptiveOptics
Commissioning
Engineering
FLAO
Instrumentation
LBTI
Main
MountainOperations
Operators
PartnerObserving
ProjectManagement
Safety
Sandbox
Software
SummerShutdown
System
Copyright © by the contributing authors. All material on this collaboration platform is the property of the contributing authors.
Ideas, requests, problems regarding Foswiki?
Send feedback