Found one power supply in failure mode (red light, switch noise) and switch bcu powering up and down.

FOund neutral missing into the wall panel.

Found a fiber of crate #2 broken (cabinet side)

Substituted temporarily with a patch-cord and a junction. FIXED

Fastlink correctly working.

Shell set at zenith and default flat applied: no issues.

STATUS:

(DATA in /home/aosup/adopt/measures/adsec_calib/status_save/20121118_194749/status_save_first_asm_set.sav,

/home/aosup/adopt/measures/adsec_calib/status_save/20121118_201133/status_save_gap_zenith.sav)

Found limit for TSS at 11 m/s. should be 8 .... investigating...found. hysterisis set at 3 m/s. all good.

TSS test: $ADOPT_MEAS/adsec_calib/spi/20121118_203838/- disabled

adsec_calib/spi/20121118_204835/- enabled

TURBULENCE:

- fqp: c

idlctrl.L |INF| 2139|2012-11-19 00:05:20.660821| MAIN > Min,Max, RMS Force Hist [N]: 0.079 0.105
idlctrl.L |INF| 2139|2012-11-19 00:05:20.660821| MAIN > . Min,Max, Pos Hist [um]: -1.8 1.7
idlctrl.L |INF| 2139|2012-11-19 00:05:20.660821| MAIN > . Min,Max Force Total [N]:-0.569 0.457
idlctrl.L |INF| 2140|2012-11-19 00:05:20.660847| MAIN > Min,Max Pos Total [um]: 53.0 62.4

data: /home/aosup/adopt/measures/adsec_calib/disturbance/20121119_001722/telescope_CR_90deg_disturb_1000hz_TS5.sav (zenith)

NOISE (high gains):

/home/aosup/adopt/measures/adsec_calib/noise/20121119_002110/noise_lin_.sav

/home/aosup/adopt/measures/adsec_calib/noise/20121119_002243/noise_nolin_.sav

STEP:

home/aosup/adopt/measures/adsec_calib/step/20121119_002640 - slowest 1.14 ms (piston, mode #4)

- ISTRUZIONI -

Ulteriori istruzioni:
- Per installazione configurazione :
- si modificano i file di test in $ADOPT_SOURCE/conf/XXX
- in $ADOPT_SOURCE si fa make install-conf
- in $ADOPT_SOURCE/PyModules si deve fare make install

- Step script: (va configurato prima in conf/adsec/Mag/scripts/step_default.txt
- print, fsm_set_flat(/ff, /no_flat)
- filename = '/home/AOeng/sup/conf/adsec/Mag/TS1/gain_60um.txt'
- print, ramp_gain_script(filename,adsec.act_w_cl)
- .r step_script

- Storia temporale: (va configurato prima in
conf/adsec/Mag/scripts/step_default.txt
- print, fsm_set_flat(/ff, /no_flat)
- filename ='/home/aosup/Source/Magellan/conf/adsec/585m/TS1/gain_60um.txt'
- print, ramp_gain_script(filename,adsec.act_w_cl)
- histfile =
'/home/AOeng/adopt/V00/conf/adsec/672b/data/layer_phi_000000_time_hist_armando_672a.sav'
- print, test_time_hist2(hist = histfile)

OR

- histfile='/home/aosup/adopt/current/calib/adsec/585m/CMD/disturb/dist_mag585_atm_s0.8_L040.0_v15.0_ovfreq1000.00_sd1983.fits'

-print, test_time_hist2(hist=histfile, /SOUND)