Day time

Retroreflector intallled in order to continue testing posible rips and preset/acquire/close loop sequence.

M2 position: 0 1.7 3.2 -290 -51 0

Closed the loop.

Changes related to auto drift:

- We tried different changes on the slopecompctrl in order to eliminate the rip during a dark setting, still we did not reach to the 100% fail free configuration, but as the antidrift is required we added a condition to the opticalloop diagn for a minumun allowed period of time between corrections, configurable trough the config file and now set to 30 secs.This seems to have a strong effecto on the BCU39 freezes.

- Also as the drift amount displayed on the GUI was not clear as it's refered to the original dark, we added that it shows the todal drift difference from the last correction.

Night time

Telescope open and ready for preset 03:20 (20:20 local time)

Preset Pisces 13


03:30 Preset from IIF

03:31 Preset failed, timeout waiting slopecompctrl.decimation.cur

03:35 Power off arrived to WFS! Later tood some time to recover (CCD39/47 in strange states)

03:51 WFS restarted, manual Preset from AOS GUI OK.

03:53 Acquire Ref, manual from AOS GUI Ok

03:53 StartAO Ok (first forgot to set the gain)


03:55 Preset Ok - Acquiref Failed (03:56:59 Shell RIP) - During enable fastlink apparently

04:10 Done manually, closed loop, autogain, ok!

NOTE: Even though the optloopdiag diag sets the dark at min each 30 sec, the slopcomctrl is not on sync and sets it even after one after.

Autogain done twice, changes a little but also did the seeing.

04:17 Done acq Pisces_SR (exp, offset, exp, stopao, exp):

20110621_041656 Pisces off center (dark)

20110621_041924 Pisces after offset (centered)

20110621_042051 Pisces open loop

SR measured on the off-axis (not-saturated) star!

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_041656 PISCES13 9.9 67 - NaN 0.99 092604 1 400 990 1.7 1.7 1.0 3 66 ON 0.0 FeII 1.64 um 1000 10 ONSKY NO acq. for DARK
20110621_041924 PISCES13 9.8 66 - NaN 0.88 092604 1 400 990 1.7 1.7 1.0 3 69 ON 59.5 FeII 1.64 um 1000 10 ONSKY NO - Background correction failed
20110621_042051 PISCES13 9.8 66 - 0.97 0.37 092604 1 400 990 -1.0 -1.0 -1.0 3 70 ON - FeII 1.64 um 1000 10 ONSKY NO OL data
olpsf_clpsf_2.png

NOTE: Better to disable camera lens tracking during offset?

04:24 Preset from IIF, Ok

04:25 AcquireRefAO from hay hay hay hay hay F, Ok but skip frames skipped on StartAO (Gain too low?)

04:31 Preset again, changed table _PISCES_ACE_AO.txt to set gain 0.3, OK!

Autogain 1.5 0.6 0.6

Pisces measured again on same star after new preset.

20110621_044218 Pisces off center (dark)

20110621_044442 Pisces after offset (centered)

20110621_044611 Pisces open loop

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_044218 PISCES13 10.0 62 - 0.94 0.60 092604 1 400 990 1.5 0.6 0.6 3 59 ON 0.0 FeII 1.64 um 1000 10 ONSKY NO acq. for DARK
20110621_044442 PISCES13 10.0 62 - 1.14 0.80 092604 1 400 990 1.5 0.6 0.6 3 59 ON 72.6 FeII 1.64 um 1000 10 ONSKY NO  
20110621_044611 PISCES13 11.9 62 - 1.17 *** 092604 1 400 990 -1.0 -1.0 -1.0 3 11 ON - FeII 1.64 um 1000 10 ONSKY NO OL data. WRONG!

04:48 Preset again, changed table _PISCES_ACE_AO.txt to set gain 0.3, OK!

Autogain 1.29 0.7 0.6

Pisces measured again on same star after new preset.

20110621_045336 Pisces off center (dark)

20110621_045554 Pisces after offset (centered)

20110621_045723 Pisces open loop

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_045336 PISCES13 10.0 60 - 0.94 0.63 092604 1 400 990 1.3 0.7 0.6 3 57 ON 0.0 FeII 1.64 um 1000 10 ONSKY NO acq. for DARK
20110621_045554 PISCES13 10.0 60 - 1.02 0.64 092604 1 400 990 1.3 0.7 0.6 3 57 ON 69.6 FeII 1.64 um 1000 10 ONSKY NO  
20110621_045723 PISCES13 12.7 59 - 1.14 *** 092604 1 400 990 -1.0 -1.0 -1.0 3 5 ON 0.0 FeII 1.64 um 1000 10 ONSKY NO OL data. WRONG!


New Preset: AO 522

Preset ok, acq ok, autogain ok.

05:27 Then big crash on WFS at the level of message deamon aparently

pyarg not connected, tried several workarounds, w_stop/w_start did not work (no connection on the other end errors), did adsc_stop/adsc_start (which implied reinit hexapod) did not help, w_stop/w_start again now doing off to the hardware and restarting (operate), then it worked!

clist during the error:
THRDTEST cmd: clist
THRDTEST MsgD client list:
   mirrorctrl.R (Clnt) [Id=3 N.Conn=2] 1.0 [TH](Built: May 29 2011 01:42:53) R  NW  @=127.0.0.1:47710 Start:2011-06-21 05:26:06.681380
   pinger.R (Clnt) [Id=4 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:16) R  NW  @=127.0.0.1:47122 Start:2011-06-21 03:45:22.532600
   masterdiagnostic.R (Clnt) [Id=5 N.Conn=1] 1.0 [TH](Built: Jun  3 2011 17:28:14) R  NW  @=127.0.0.1:47123 Start:2011-06-21 03:45:23.050857
   slopecompctrl.R (Clnt) [Id=6 N.Conn=2] 1.0 [TH](Built: Jun 21 2011 03:59:57) R  NW  @=127.0.0.1:43859 Start:2011-06-21 04:00:22.532416
   techviewctrl.R (Clnt) [Id=7 N.Conn=1] 1.0 [TH](Built: Jun 19 2011 00:31:23) R  NW  @=127.0.0.1:47125 Start:2011-06-21 03:45:24.071814
   powerboard.R (Clnt) [Id=8 N.Conn=1] 1.0 [TH](Built: Jun 10 2011 23:21:32) R  NW  @=127.0.0.1:47126 Start:2011-06-21 03:45:24.588573
   picctrl.R (Clnt) [Id=9 N.Conn=1] 1.0 [TH](Built: Jun 10 2011 23:21:32) R  NW  @=127.0.0.1:47127 Start:2011-06-21 03:45:25.098878
   ccd39.R (Clnt) [Id=10 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:19) R  NW  @=127.0.0.1:47128 Start:2011-06-21 03:45:25.621445
   ccd47.R (Clnt) [Id=11 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:19) R  NW  @=127.0.0.1:47129 Start:2011-06-21 03:45:26.125923
   ttctrl.R (Clnt) [Id=12 N.Conn=1] 0.0 (Built: May 29 2011 01:16:15) R  NW  @=127.0.0.1:47130 Start:2011-06-21 03:45:26.637042
   adc1.R (Clnt) [Id=13 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:17) R  NW  @=127.0.0.1:47133 Start:2011-06-21 03:45:27.150285
   adc2.R (Clnt) [Id=14 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:17) R  NW  @=127.0.0.1:47135 Start:2011-06-21 03:45:27.663497
   filterwheel1.R (Clnt) [Id=15 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:17) R  NW  @=127.0.0.1:47137 Start:2011-06-21 03:45:28.177028
   filterwheel2.R (Clnt) [Id=16 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:17) R  NW  @=127.0.0.1:47140 Start:2011-06-21 03:45:28.691811
   rerotator.R (Clnt) [Id=17 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:17) R  NW  @=127.0.0.1:47144 Start:2011-06-21 03:45:29.204582
   mercury.R (Clnt) [Id=18 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:17) R  NW  @=127.0.0.1:47148 Start:2011-06-21 03:45:29.718436
   cubestage.R (Clnt) [Id=19 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:17) R  NW  @=127.0.0.1:47151 Start:2011-06-21 03:45:30.233811
   baysidex.R (Clnt) [Id=20 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:18) R  NW  @=127.0.0.1:47154 Start:2011-06-21 03:45:30.747703
   baysidey.R (Clnt) [Id=21 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:18) R  NW  @=127.0.0.1:47156 Start:2011-06-21 03:45:31.261405
   baysidez.R (Clnt) [Id=22 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:18) R  NW  @=127.0.0.1:47160 Start:2011-06-21 03:45:31.775900
   cameralensctrl.R (Clnt) [Id=23 N.Conn=1] 1.0 [TH](Built: May 29 2011 01:16:14) R  NW  @=127.0.0.1:47163 Start:2011-06-21 03:45:32.290900
   housekeeperWFS.R (Clnt) [Id=24 N.Conn=1] 0.1 [TH](Built: May 29 2011 01:18:06) R  NW  @=127.0.0.1:47167 Start:2011-06-21 03:45:32.805091
   optloopdiag.R (Clnt) [Id=25 N.Conn=1] 0.1 [TH](Built: Jun 21 2011 01:14:57) R  NW  @=127.0.0.1:47169 Start:2011-06-21 03:45:33.319887
   wfscontrol.R (Clnt) [Id=28 N.Conn=1] 1.0 [TH](Built: Jun 18 2011 05:45:11) R  NW  @=127.0.0.1:47194 Start:2011-06-21 03:45:39.557368
   EngGUI0 (Clnt) [Id=29 N.Conn=1] 0.0 (Built: May 29 2011 01:16:12) NR NW  @=127.0.0.1:47232 Start:2011-06-21 03:45:50.288739
   pupilcheck39.R (Clnt) [Id=30 N.Conn=12] 0.0 (Built: May 29 2011 01:16:12) R  NW  @=127.0.0.1:33675 Start:2011-06-21 05:19:12.022331
   CCDVIEWccd3900 (Clnt) [Id=32 N.Conn=1] 0.0 (Built: May 29 2011 01:16:12) NR NW  @=127.0.0.1:57544 Start:2011-06-21 03:50:13.810433
   CCDVIEWccd4700 (Clnt) [Id=33 N.Conn=1] 0.0 (Built: May 29 2011 01:16:12) NR NW  @=127.0.0.1:57546 Start:2011-06-21 03:50:24.750892
   sysprocesses.R00 (Clnt) [Id=34 N.Conn=2] 0.0 (Built: May 29 2011 01:16:12) NR NW  @=127.0.0.1:45910 Start:2011-06-21 05:25:03.053482
   THRDTEST (Clnt) [Id=38 N.Conn=1] 6.12 [TH](Built: May 29 2011 01:16:25) NR NW  @=127.0.0.1:47834 Start:2011-06-21 05:27:26.816588

The AO522 is a double star!!! The separation is about 3.5 pixel diagonals, which is about 80 mas. SR cannot be computed on this object....

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_060756 AO522 14.1 68 - 1.58 1.18 075552 3 66 312 3.7 2.8 2.8 6 41 ON 0.0 FeII 1.64 um 10000 1 ONSKY NO acq. for DARK
20110621_060926 AO522 14.1 68 - 1.38 1.35 075552 3 66 312 3.7 2.8 2.8 6 40 ON ? FeII 1.64 um 10000 1 ONSKY NO double Star!
20110621_060952 AO522 14.1 68 - 1.44 0.92 075552 3 66 312 -1.0 -1.0 -1.0 6 40 ON 0.0 FeII 1.64 um 10000 1 ONSKY NO OL data
olpsf_clpsf_3.png

06:30:56 Shell RIP due apparently to the fastlink enable (!!!)

06:36:00 BCU/CCD 39 freezed

06:42:20 Shell RIP (loop freq 312 OVS freq 290)

AO663

New strategy of analysis: "You are my dark, and I am yours".

tr = ['20110621_075648','20110621_075834','20110621_075911']
setdark = obj_new('aodataset', tr[0])
pisces_save_dark, setdark
setdark = obj_new('aodataset', tr[1])
pisces_save_dark, setdark
ao = getaoelab(tr[0], dark_fname=tr[1]+'.fits_cube.fits',/rec)
ao = getaoelab(tr[1], dark_fname=tr[0]+'.fits_cube.fits',/rec)
ao = getaoelab(tr[2], dark_fname=tr[1]+'.fits_cube.fits',/rec) ; chosen dark depends on where the f*#k Javier placed the PSF (if not blurred).
TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_075648 AO663 15.5 83 - NaN 1.34 083227 4 36 200 2.0 2.0 2.7 6 36 ON 1.7 FeII 1.64 um 20000 1 ONSKY NO  
20110621_075834 AO663 15.4 83 - NaN 1.05 083227 4 36 200 2.0 2.0 2.7 6 38 ON 2.9 FeII 1.64 um 20000 1 ONSKY NO  
20110621_075911 AO663 18.9 83 - NaN - 083227 4 36 200 -1.0 -1.0 -1.0 6 2 ON - FeII 1.64 um 20000 1 ONSKY NO OL data. WRONG!
NOTE: As usual, the OL acquisiton is crap because an offset is applied while acquiring.... Furthermore, David doesn't manage to keep the DIMM up and running...

New acquisition:

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_081157 AO663 15.4 84 - NaN 1.07 083227 4 36 200 3.6 2.6 3.6 6 39 ON 1.5 FeII 1.64 um 20000 1 ONSKY NO  
20110621_081401 AO663 15.6 84 - NaN 1.80 083227 4 36 200 3.6 2.6 3.6 6 32 ON 0.9 FeII 1.64 um 20000 1 ONSKY NO  
20110621_081440 AO663 15.8 84 - NaN *** 083227 4 36 200 -1.0 -1.0 -1.0 6 27 ON ** FeII 1.64 um 20000 1 ONSKY NO OL data. Ancora merda.

AO662

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_083019 AO662 15.7 78 - 1.53 1.59 083227 4 36 100 2.6 1.7 2.6 6 61 ON 0.7 FeII 1.64 um 20000 1 ONSKY NO - Background correction failed
20110621_083217 AO662 15.7 77 - 1.45 1.54 083227 4 36 100 2.6 1.7 2.6 6 59 ON 0.9 FeII 1.64 um 20000 1 ONSKY NO - Background correction failed
20110621_083316 AO662 19.2 77 - 1.33 *** 083227 4 36 100 -1.0 -1.0 -1.0 6 2 ON -- FeII 1.64 um 20000 1 ONSKY NO - Pupils not on target
olpsf_clpsf1_clpsf2.png

New acquisition:

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift FHWM filter exp #frames disturb SN notes
20110621_085420 AO662 15.6 73 - 1.36 1.75 083227 4 36 200 3.6 1.7 2.6 6 32 ON 0.63" FeII 1.64 um 30000 1 ONSKY NO  
20110621_085555 AO662 15.7 73 - 1.46 1.96 083227 4 36 200 3.6 1.7 2.6 6 29 ON ? FeII 1.64 um 30000 1 ONSKY NO  
20110621_085648 AO662 18.5 73 - 1.57 *** 083227 4 36 200 -1.0 -1.0 -1.0 6 2 ON 0.97" FeII 1.64 um 30000 1 ONSKY NO OL data
olpsf_clpsf4.png

Si cambia stellina:

AO659

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter expSorted ascending #frames disturb SN notes
20110621_094117 AO659 13.1 76 - 1.49 1.03 180534 2 145 400 5.4 2.7 1.1 3 36 ON 8.8 FeII 1.64 um 10000 1 ONSKY NO  
20110621_094319 AO659 13.1 75 - NaN 1.01 180534 2 145 400 5.4 2.7 1.1 3 37 ON 18.2 FeII 1.64 um 10000 1 ONSKY NO  
20110621_094353 AO659 20.6 75 - 1.04 *** 180534 2 145 400 -1.0 -1.0 -1.0 3 0 ON -- FeII 1.64 um 10000 1 ONSKY NO  

New acquisition:

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_100054 AO659 13.0 73 - 1.16 1.04 180534 2 145 400 3.5 1.7 1.1 3 38 ON 29.9 FeII 1.64 um 10000 1 ONSKY NO  
20110621_100222 AO659 13.0 72 - NaN 0.97 180534 2 145 400 3.5 1.7 1.1 3 39 ON 29.2 FeII 1.64 um 10000 1 ONSKY NO  
20110621_100256 AO659 13.0 72 - NaN 0.64 180534 2 145 400 -1.0 -1.0 -1.0 3 40 ON -- FeII 1.64 um 10000 1 ONSKY NO OL data. GOOD!

New acquisition:

TrackNo RefStar Mag El Wind DIMM/OL Rec bin #mod freq gain mod nph AntiDrift SR filter exp #frames disturb SN notes
20110621_101106 AO659 13.0 71 - 1.14 0.73 180534 2 145 400 3.5 1.7 1.1 3 41 ON 41.3 FeII 1.64 um 5000 2 ONSKY NO  
20110621_101253 AO659 13.0 71 - NaN 0.85 180534 2 145 400 3.5 1.7 1.1 3 40 ON 36.6 FeII 1.64 um 5000 2 ONSKY NO  
20110621_101334 AO659 19.7 70 - NaN *** 180534 2 145 400 -1.0 -1.0 -1.0 3 0 ON 540.0 FeII 1.64 um 5000 2 ONSKY NO OL data. WRONG!

-- JavierArgomedo - 21 Jun 2011

Topic attachments
I Attachment Action Size Date Who Comment
olpsf_clpsf1_clpsf2.pngpng olpsf_clpsf1_clpsf2.png manage 202 K 21 Jun 2011 - 11:15 UnknownUser  
olpsf_clpsf4.pngpng olpsf_clpsf4.png manage 140 K 21 Jun 2011 - 11:55 UnknownUser  
olpsf_clpsf_2.pngpng olpsf_clpsf_2.png manage 110 K 21 Jun 2011 - 05:01 UnknownUser  
olpsf_clpsf_3.pngpng olpsf_clpsf_3.png manage 134 K 21 Jun 2011 - 06:38 UnknownUser  
This topic: FLAO > WebHome > LbtTel > Flao1andFlao2DetailedLogAtTelescope > LabLog20110620
Topic revision: 11 Sep 2012, EnricoPinna
This site is powered by FoswikiCopyright © by the contributing authors. All material on this collaboration platform is the property of the contributing authors.
Ideas, requests, problems regarding Foswiki? Send feedback