HOWTO Force the stop of slope flow from WFS

Go to wfsdx or wfssx workstation. After logged in, follow the steps:

  • call the script vartool_AO.py
  • find the variable slopecompctrl.L.FASTLINK.ENABLE.REQ
  • change its value from 1 to 0
  • go to the adsecdx or adsecsx workstation
  • from engineering GUI call a stopAO button. If not available, call from an IDL terminal the stopAO procedure: print, fsm_stop_ao()
  • stop and start AdsecArbitrator from adsec SysProcesses GUI

-- %USERSIG{MarcoXompero - 2014-06-27}%