SX AO Commissioning

When setting the shell from the Adsec control gui, the AOS gui didn't show the shell as being set. We had a CCD39 "Not Live" error at the beginning of the night. I restarted the Adsec and W-unit software.

02:05 All seems to be functioning normally.

Fri Oct 21 02:08:22.814 2016 aos.Pause{FLAO}.failed - Pause{FLAO}[22] - Illegal command for state AOArbitrator.Ready

Unknown Error during offset. The Bayside stages seem to be fine.

Actuator # 367 might be acting up.

Fri Oct 21 02:27:47.566 2016 aos.Pause{FLAO}.failed - Pause{FLAO}[22] - FLAO: unknown exception from arbitrator

02:31 Optical gain ratio became very low during a pause and the shell ripped during resume because the gains were out of whack.

02:38 Intervention Mode

Fri Oct 21 02:46:06.733 2016 aos.OffsetXY{FLAO}.failed - OffsetXY {FLAO}[101] - [AOException] RETRY: Offset outside FoV limits. Target xyz is -441.72 -54.31 54.60 (-5002) VALUE_OUT_OF_RANGE_ERROR

02:51 GOPT Oscillating ratio between 0.1 and 1.5

02:52 Now it's stable and around 1 (after applying it, naturally)

02:56 Loop opened for unknown reason. I reclosed it with the FLAO gui and reset the gains.

05:03

-13006 - [Exception] exception ::Ice::UnknownUserException { unknown = AODefs::AOException }

-13006 - No connection to AdSec

-13006 - No connection to AdSec

-13006 - No connection to AdSec

-13006 - Illegal command for state LoopFault

-13006 - Illegal command for state LoopFault

-13006 - Illegal command for state LoopFault

-13006 - Illegal command for state LoopFault

03:18 Actuators 367 and 148 have jumped many times, possibly causing skip fames to open the loop. I took them out of the files, but haven't had a chance to restart the system. I saw them in the FLAO GUI. During more than one session with the loop closed.