Troubleshoot ARGOS

Troubleshoot by states

More recover procedures at: HowToRecoverArgos
When Symptom What to do Notes
Cold start PowerOn fails, several devices are still unreachable (e.g. the LGSW rack is off). The Remote Power Switch (in las lab GUI) is unresponsive HowToPowerCycleTheRemotePowerSwitch  
LGS acquired LGS acquisition is unstable. Sporadic, large oscillations of the LGSW image on the patrol cameras. HowToCheckVibrationCompensationAccelerometers  

When Where What Why Solution
With POWERING_UP SX back to UNKNOWN blue patrol camera does not connect when cold press again power_up
With POWERING_UP DX time out exception CCD is taking to long to cool down press OK, and in case it goes back to UNKNOWN press again POWER_UP
With POWERING_UP ANY time out exception various reasons press OK, press again POWER_UP
With POWERING_UP ANY ERROR 'None Type' object has no attributes 'event Power up' AArb is not connected with AOS enable AArb in AOS GUI
With ANY ANY Any ERROR with 'None Type' This is an indication, that connection to the database is lost, either TaN or AOS. For AOS, enable AArb in AOS GUI or restart ARGOS arbitrator.
With PREPARING ANY NOTICE: ...."Timeout waiting for slopecompctrl.R.CONFIG.CUR (-5001) TIMEOUT_ERROR".... FLAO slope computer error

Go FLAO "System process" GUI check and restart:

  • Slope computer Ctrl
  • CCD39 controller
  • Pupil check ccd39
With PREPARING ANY ... Error in key managment... Truth sensor process died. Go FLAO "System process" GUI: check and restart.

Troubleshoot by Device

WFS CCD

Device What How to diagnose Solution
WfsCamera Is not switched on. In LGSW Lab GUI, 'WFS.PnCCDStatus' is 'Unknown', but camera is cold and everything in 'WFS.Debug Statuses' looks ok In 'WFS.Parameters Settings' click on "Power ON CCD"  
WfsCamera Fails at Power Up with "Cannot turn cooling on. Check statuses." In LGSW Lab GUI, WFS tab, check "Debug Statuses" tab. If any of the PSU Statuses is red, power off the cabinet for ~10 minutes (to ensure PSU is completely off). Power on and try again. IT#7960.

LM1

What How to diagnose Solution
Movements not as expected

LAT images,

log files of LM (~/log/?X.LAN.LM1.BASDARD.log or ?X.LAN.CONTROLLER.log),

check absolute encoder in argos_?x_lm1_tripod_gui !!never ever use another GUI for moving the LM1!!

Look into Zabbix screen "?X LM1 devices"

depends

Use:

LAN controller GUI to set to nominal postion (only in state "Ready to Observe")

Tripod GUI to check absolute encoders and move LM1

LAN

WhatSorted descending How to diagnose Solution
LAN fails to complete Power On Check if NI_BOX is reachable If NI_BOX is not reachable, go to the corresponding LLP cabinet and press the power switch (lower left of the unit) to the "STANDBY" position and then back to "ON". See IT#8411

-- LorenzoBusoni - 29 Nov 2017

This topic: ARGOS > WebHome > TroubleShoot
Topic revision: 09 Jul 2021, GustavoRahmer
This site is powered by FoswikiCopyright © by the contributing authors. All material on this collaboration platform is the property of the contributing authors.